Section B: Control Operation
HEAT DEMAND
A heat demand is required in order for the control to provide heat by firing the boiler and opening the 3-way diverting valve. To
generate a heat demand, apply between 24 and 240 V (ac) across the Heat Demand terminals (1 and 2). Once voltage is applied,
the Demand pointer is displayed in the LCD.
When the heat demand is removed, the 3-way diverting valve is fully closed before the control is allowed to register a new heat
demand. The Demand pointer will be displayed whenever voltage is present on the Heat Demand terminals, even if the heat
demand is not registered. The 3-way diverting valve is closed to ensure the boiler is protected in the next boiler cycle.
Optionally, the control can be set up to target a setpoint mix supply temperature or outdoor reset temperature through the diverting
valve.
OUTDOOR RESET RATIO
When the control is used as a mixing reset control, the control uses
an outdoor sensor to measure the outdoor temperature. The reset
ratio increases the mix water temperature for every degree the outdoor
temperature falls. The slope of the reset ratio determines the rate at
which the temperature increases with falling outdoor temperatures.
The reset ratio is adjustable using the mix design (MIX DSGN) and the
outdoor design (OUTDR DSGN) settings.
Fixed PointFixed Point
By Changing
the Mix Design
and the Outdoor
Design settings
the Reset Ratio
changes.
By Changing
the Mix Design
and the Outdoor
Design settings
the Reset Ratio
changes.
70˚F
70˚F
Outdoor Reset
When the outdoor design (OUTDR DSGN) setting is set to a temperature, the control calculates a mix supply temperature based
on the outdoor air temperature and the programmed reset ratio. An outdoor sensor and a mix supply sensor must be installed.
Setpoint Control
When the outdoor design (OUTDR DSGN) setting is set to OFF, and there is a mix supply sensor installed, the control supplies a
fixed mix supply temperature equal to the MIX TARGET setting. An outdoor sensor is not required during this mode of operation.
No Diverting Valve
If a diverting valve is not installed, the outdoor design (OUTDR DSGN) is set to OFF. The boiler return sensor must be installed
to provide monitoring of the boiler conditions.
Floating Action
A 24 V (ac) floating action actuator motor is connected directly to the control on the R, R and N terminals (9, 10 and 11). The
R on terminal 9 is used to open the 3-way diverting valve to the system. The valve can open either in the clockwise or the
counterclockwise direction depending on the orientation of the valve. The R on terminal 10 is used to close the valve. The control
pulses the actuating motor to open or close to maintain the correct mixed supply water temperature at the mix sensor when
there is a heat demand. A visual indication as to whether the control is currently opening or closing the 3-way diverting valve is
displayed in the LCD.
Boiler Protection
The control is capable of providing boiler protection from cold return water temperatures. If the boiler sensor temperature is
cooler than the BOIL MIN setting while the boiler is firing, the control reduces the output to the 3-way diverting valve. This limits
the amount of cool return water to the boiler and allows the boiler temperature to recover. This feature can only be used if a 3-way
diverting valve is installed.
Exercising
The control has a built-in exercising function. If the boiler recirculating pump or valve has not been operated at least once every
3 days, the control turns on the output for a minimum of 10 seconds. This minimizes the possibility of a pump or valve seizing
during a long period of inactivity. The control ensures that the diverting valve operates over its entire range at least once each
exercising period. While the control is exercising, the Test LED flashes.
Note: The exercising function does not work if power to the control, pump, or valve is disconnected.